WENZHOU SANTUO ELECTRICAL CO.,LTD.

Reputation is the first, quality is the priority.

Manufacturer from China
Site Member
7 Years
Home / Products / MCB Circuit Breaker /

RCBO 50 / 60hz Type A Model Residual Circuit Breaker With Over Current Protection

Contact Now
WENZHOU SANTUO ELECTRICAL CO.,LTD.
City:wenzhou
Province/State:zhejiang
Country/Region:china
Contact Person:MrSunny Zhang
Contact Now

RCBO 50 / 60hz Type A Model Residual Circuit Breaker With Over Current Protection

Ask Latest Price
Video Channel
Brand Name :SONTUNE
Model Number :A
Certification :CE, CB, SAA,ISO9001
Place of Origin :China
MOQ :1000PCS
Price :Negotiable
Supply Ability :3000PCS/DAY
Delivery Time :25DAYS
Packaging Details :100PCS/CTN
Ue :230/400V
Standard :IEC61009
Breaking Capacity :3KA,4.5KA,6KA
Type :RCBO
Credential :CE,CB,SAA, ISO9001
color :PA66
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

RCBO 50 / 60hz Type A Model Residual Circuit Breaker With Over Current Protection

STRO7-63 Series A model RCBO:

STRO7-63 series high breaking capacity Residual current Circuit Breaker with over current protection is used in AC50/60Hz, rated voltage of 230V

2, 4 poles 400V, rated current to 63A for overload and short-circuit protection and Leakage current protection as well as for unfrequented switching under normal case.It is used extensively for industry, commercial and household.This product conform to IEC61009 standard.


General
Application:For protecting cables and equipments against overload and short circuit. General rules for choosing RCBO .

Technical data of the network at the point considered

The earthing systems,short-circuit current at the circuit breaker installation point,which must always be less than the breaking capacity of this device,network normal voltage.

Model A RCBO (electrical type, magnetic type)
Standard IEC61009
Pole 2P, 4P
Rated Short-circuit capacity(Icn) 3KA,4.5KA,6KA
Rated Current(In) 16,20,25,32,40,50,63A
Rated Voltage(Un) AC230(240)/400(415)V
Rated Frequency 50/60HZ
Tripping curve B,C,D
Magnetic releases B curve: between 3and 5 In
C curve: between 5and 10In
D curve: between 10 and 14In
Electro-mechanical endurance over 6000 cycles



Standard IEC/EN 61009
Electrical
features
Rated current In A 16,20,25,32,40,50,63
Poles P 2, 4
Rated voltage Ue V AC 240/415
Insulation voltage Ui V 500
Rated frequency Hz 50/60
Rated breaking capacity A 4500 ;6000
Rated impulse withstand voltage(1.2/50)Uimp V 4000
Dielectric test voltage at ind.Freq.for 1 min Kv 2
Pollution degree 2
Thermo-magnetic release characteristic B,C,D
Mechanical
features
Electrical life t 4000
Mechanical life t 10000
Protection degree IP20
Reference temperature for setting
of thermal element
30
Ambient temperature
(with daily average ≤35℃)
-5~+40(Special application please refer to
temperature compensation correction)
Storage temperature -25~+70
Installation Terminal connection type Cable/Pin-type busbar
Terminal size top/bottom for cable mm2 25
AWG 18-3
Therminal size top/bottom for busbar mm2 25
AWG 18-3
Tightening torque N*m 2
In-lbs 18
Mounting on DIN rail EN 60715(35mm)by means of fast clip device
Connection From top and bottom

Discount and promotion price is available.
Technology support is available.

Inquiry Cart 0